Proprietary Energy On system

Renewable‑Assisted DHW System

(RA-DHW)

Lower-cost hot water in district-heated buildings, with no disconnection from the network and no change for residents.

RA-DHW is Energy On’s proprietary solution that turns a district heating substation into a hybrid source of domestic hot water (DHW). It connects a heat pump, PV, battery storage and DHW buffer tanks to the existing substation, while the control system continuously selects the cheapest way to heat the water.

Energy On app — live view
This is what our app looks like: PV output, grid import, battery status and water temperatures at every point of the system, in real time.

The heat pump as the first heating stage

The heat pump is connected in series upstream of the substation’s heat exchanger. Cold mains water at around 10°C first enters the buffer tanks charged by the heat pump, and only then flows to the heat exchanger. The heat pump therefore works where it reaches its highest efficiency, and the substation tops up the temperature only when needed.

Mains water
Cold water entering the system
~10°C
→
Heat pump
Heats from a low temperature, at the highest COP
stage 1
→
DHW buffer tanks
Thermal storage for peak demand hours
storage
→
District heating substation
Tops up only the missing temperature difference
stage 2
→
Apartments
Always the same DHW set-point temperature
~55–60°C

The system operates in three modes

Full heating by the heat pump

With good sunshine and warmer air, the heat pump reaches the target temperature on its own, and the water simply flows through the substation.

Pre-heating

The heat pump raises the temperature to a cost-effective level, and the substation tops the water up to the set-point.

Substation-only operation

Depending on the heat price, during frost, without sunshine or when electricity is expensive, the substation can take over all of the heating.

Switching between modes is automatic and seamless, and the tap water temperature stays constant.

Control that calculates the cost of heat

The system does not follow a fixed schedule. It continuously analyses data from the whole installation and decides which source should heat the water.

What it analyses

RA-DHW
control
(EMS)

calculates the cost of heat from each source

What it decides

The system is also ready to operate under dynamic electricity tariffs.

Three ways to use PV energy

PV surplus stays in the building:

1

Directly

As power for the heat pump.

2

In the battery

For later use.

3

In the water

As heat stored in the DHW buffer tanks, the cheapest energy storage in the system.

Case study

Szafranka 18, Słupsk: 12 months of measurements

This building, owned by the Słupsk Social Housing Society (STBS), was the pilot installation of RA-DHW. After a year of operation, the investor ordered the same solution for two more buildings.

−41%
cost of heating 1 m³ of DHW: from PLN 36.35 to PLN 21.48
3.32
average annual COP
58%
of DHW from the heat pump
15.01 t
less CO₂ per year
1 → 3
STBS buildings after the pilot
12 months of operation

Measured data: August 2025 – July 2026

A full operational year, including the extreme winter conditions of January and February 2026. All values come from data measured by the EMS, not from catalogue specifications.

3.32
average annual COP (SCOP)
160 GJ
of heat delivered by the heat pump (44,447 kWh)
15.01 t
CO₂ emission reduction / year
PLN 17,292
savings in one building / year

Monthly heat output and COP

44,447 kWh of heat / 13,379 kWh of electricity
0 1000 2000 3000 4000 2.5 3.0 3.5 4.0 4.5 4,453 4,106 4,351 4,143 4,254 3,667 2,888 3,524 3,459 2,214 3,407 3,981 4.21 2.83 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
heat delivered by the heat pump [kWh] monthly COP

Cost of heating 1 m³ of DHW

Before — district heating onlyPLN 36.35
After — hybrid systemPLN 21.48
−41%
approx. PLN 17,292 saved per year in a single building, with residents’ comfort fully maintained

CO₂ emission balance

regional network emission factor: 115.58 t CO₂/TJ
Emissions avoided on the district heat side+18.49 t
Additional emissions — grid electricity for the heat pump−3.48 t
Net annual effect15.01 t CO₂

Share of DHW demand covered

58% heat pump
Heat pump — 58.1% of annual DHW
District heating (peak load) — 41.9%

Renewable energy share

68.3% PV self-consumption
PV energy used on site — 68.3%
Surplus exported to the grid — 31.7%
Where the heat pump’s electricity comes from
52.9% from PV / battery47.1% from the power grid
technical specification

What the Słupsk system consists of

12kW
Air-to-water heat pump
Panasonic Aquarea T-CAP Gen. K, R32 refrigerant
10.67kWp
PV installation
Powers the heat pump directly and charges the battery
10.24kWh
Battery storage (BESS)
Shifts PV energy to the evening hours
1000l
DHW buffer tanks
Thermal storage upstream of the substation’s heat exchanger
Hydraulic layout
Heat pump in series upstream of the heat exchanger
Control
Proprietary EMS with SCADA monitoring
Service
DHW preparation
Investor
STBS, ul. Szafranka 18, Słupsk
Contractor
Energy On Sp. z o.o.
Funding
Own funds and the “OZE Grant” programme
project photos

Gallery: Szafranka 18, Słupsk

The building with PV on the roof
Heat pump outdoor unit
Plant room and DHW buffer tanks
Inverter and battery storage
Battery storage modules
Other installations

The same system operating in further buildings

The hydraulic layout and control system are identical in every installation. Only the heat pump capacity, PV output and storage sizes change. Click an installation to see the details.

Plant room with DHW buffer tanks and heat pump indoor units, ul. Gnieźnieńska 17A and 17B, Bydgoszcz
Bydgoszcz

ul. Gnieźnieńska 17A and 17B

85-313 Bydgoszcz
Heat pump
Panasonic T‑CAP 16 kW gen. K
DHW buffer tanks
2 × 500 l
PV
16.52 kWp
Battery storage
20.48 kWh
Two heat pump outdoor units next to the building at ul. Marcina Kasprzaka 4A, Olsztyn
Olsztyn

ul. Marcina Kasprzaka 4A

10-057 Olsztyn
Heat pump
Panasonic T‑CAP 16 kW gen. K
DHW buffer tanks
3 × 500 l
PV
22.42 kWp
Battery storage
40.96 kWh
Heat pump outdoor units next to the multi-family building at ul. Franciszka Żymirskiego 7, Warsaw
Warsaw

ul. Franciszka Żymirskiego 7

04-035 Warsaw
Heat pump
2 × Panasonic T‑CAP 16 kW gen. K
DHW buffer tanks
4 × 500 l
PV
25.96 kWp
Battery storage
30.72 kWh
dji 20260511135342 0007 d
Gdańsk

“Chełm” Housing Cooperative

80-809 Gdańsk
Heat pump

5 × Panasonic T-CAP 16 kW, three-phase, K Generation + 2 × Panasonic T-CAP 12 kW, three-phase, K Generation — total capacity: 104 kW

DHW buffer tanks
8,000 litres
PV
207.18 kWp
Battery storage
343.6 kWh